Поделиться:
WTHD-HU3110 | WTHD-HU31S10 | WTHD-HU3115 | WTHD-HU31S15 | WTHD-HU3120 | WTHD-HU31S20 | |||||||
Rated power | 10KVA/9KW | 15KVA/13.5KW | 20KVA/18KW | |||||||||
Machine architecture | Double Conversion Online UPS | |||||||||||
Phases | Three-phase input / single-phase output | |||||||||||
AC Input | ||||||||||||
Input lines | Three phase four wire + protective ground or single-phase three-wire (zero/live wire + protected ground) | |||||||||||
Rated Voltage | 208/220/230/240VAC | |||||||||||
Input frequency | 50Hz/60HZ | |||||||||||
Input voltage range | ||||||||||||
Bypass voltage | 115~285VAC×(1±3%) | |||||||||||
Input power factor | ≥0.99 | |||||||||||
Battery Input | ||||||||||||
Battery voltage | 192/240V(optional) | |||||||||||
Capacity *battery number | 12V/7AH x 16pcs | external | 12V/7AH x 32pcs | external | 12V/7AH x 32pcs | external | ||||||
Backup time (half/full load) | standard:half load ≥6 minutes, full load ≥ 2 minutes (standard) long acting :depends on external battery | |||||||||||
Maximum impulse current | < 150% of rated current | |||||||||||
Battery charge time | standard model:charge to 90% in 5 hours long acting:depends on external battery pack capacity | |||||||||||
AC Output | ||||||||||||
Output mode | Single-phase 2 cables + protection ground | |||||||||||
Output Voltage | 220/230/240VAC ±2% (inverter output) | |||||||||||
Output frequency | 50/60Hz±0.5% | |||||||||||
THDV% | Sine wave THDV <2% (linear load); sine wave THDV<7% (nonlinear load) | |||||||||||
Output power factor | 0.9 | |||||||||||
Transfer time | Mains Battery mode 0ms | |||||||||||
Overload capacity | Mains/battery (240VDC) 105-125% for 10 minutes, 126-150% for 1 minute, >150% 100ms Battery (192VDC) 105-125% 1s, >126% 100ms | |||||||||||
RS232, Network monitoring card, dry contact, MODBUS monitoring card, optional | RS232, Network monitoring card, dry contact, MODBUS monitoring card, optional |