Поделиться:
Measurement function | Voltage | Reference voltage | 3*220/380V | ||||
Voltage waste | error<10VA | ||||||
Impedance | >2MΩ | ||||||
Accuracy grade | ±0.2% | ||||||
Current | Current specification | 1.5(6)A 5(60)A 20(80)A 10(100)A | |||||
Current waste | error<4VA | ||||||
Accuracy grade | ±0.2% | ||||||
Power | Active, reactive and power error±0.2% | ||||||
Grid frequency | 45-65Hz error±0.2% | ||||||
electric energy | Active power level 1&2 | ||||||
Digital signal | Electric pulse output | Active optocoupler output | |||||
Pulse constant | 6400imp/KWh 400imp/KWh | ||||||
Starting current | Connect directly | 0.004In (level 1) reactive:0.004In (level 2) | |||||
Connect by CT | 0.002Ib | ||||||
Communication | Interface and communication protocol | RS485¨ Modbus¨ DL/T 645-2007¨ | |||||
Mailing address range | Modbus 1~247 | ||||||
Baud rate | 1200bps~9600bps | ||||||
Overall dimensions | 160×112×71(mm) | ||||||
Environment | Working temperature | -25℃~60℃ | |||||
Storage temperature: | -40℃~70℃ | ||||||
Relative humidity | ≤95% | ||||||
Altitude | atmospheric pressure:63.0kPa~106.0kPa(﹤4000m above sea level )Except for special order requirements |