8 zone smoke wired conventional fire alarm control panel CK1008


 


FEATURES for the fire alarm control panel                                                                                                                                                                         

 


AC POWER

90~270 VAC, 50 Hz, 2.0 amps.

Wire size: minimum 14 AWG (2.0 mm2) with 600-volt insulation.

BATTERY

Sealed lead-acid batteries only.

Maximum charging circuit: 27.6VDC  0.8 amp for normal flat charge.

Maximum battery charger capacity: 18AH battery.

NOTE: two 4AH batteries can be housed in the cabinet. Larger

batteries require a separate battery box.

Total 24 V system power: 3.0 amps.

Notification appliance (signal) power: 2.5 amps.

Maximum current per NAC: 1.25 amps (expandable to 2.5amps).

Maximum battery charging capability: 18 AH.

Auxiliary Outputs

Resettable four-wire smoke detector power  500 mA.

Non-resettable power  500 mA.

NOTE: Total current for auxiliary power outputs and two NACs must not exceed 3.0 amps. .

Integral Form-C Alarm, Trouble and Supervisory relays, rated at: 2.0 amps  30 VDC (resistive), 2.0 amps  30VAC (resistive).

 

CABINET AND MOUNTING

CABINET PHYSICAL DIMENSIONS: 40.0 cm high x 35.0 cm wide x 11.5 cm deep.

CARTON PACKAGE DIMENSIONS: 48.0 cm high x 42.0 cm wide x 18.5 cm deep.

CABINET NET WEIGH: 6.0 Kg. (without batteries).

CABINET GROSS WEIGH: 6.6 Kg. (without batteries).

MOUNTING: The cabinet mounts using two key slots at the top of the back and two additional 6.5mm diameter holes at the bottom.

 

 