Охлажденной воды кассетного типа потолочный фанкойл


Поделиться:

Цена:206,30 $ - 226,30 $*
Стоимость в USD (на сегодня):Узнать

Количество:

Описание и отзывы

Характеристики


Chilled Water Cassette Type Ceiling Mounted Fan Coil Units


fan-coil unit.jpg


 fan-coil unit2.jpgfan-coil unit3.jpg


                                         .jpg



 


The low-noise three-speed capacitor motor of well-known domestic brands is adopted, with imported precision ultra-low-noise rolling bearing.

      fan-coil unit4.jpg


Three-dimensional spiral wind blade ensures wind volume and thinner shape, and irregular wind blade pitch greatly reduces operating noise.

 

fan-coil unit5.jpg


 


The  pipe of water collecting head adopts forged brass structure, which is reliable and durable.


111111111.jpg


 


 


Circular heat exchanger design, wind uniformity, seamless copper tube and new high-efficiency corrugated double curved open window hydrophilic aluminum foil fin, optimize flow design and effectively improve heat transfer efficiency.


fan-coil unit7.jpg


 


 


 Foam insulation, thickening foam insulation layer inside the fuselage, not easy to produce condensation beads in summer, not easy to corrode, and extend the service life.


 


fan-coil unit9.jpg


 


4-way cassette fan coil unit




















































































































































































Model and performance



 



FP-34



FP-51



FP-68



FP-85



FP-102



FP-136



FP-170



FP-204



FP-238



Rated air flow


m3/h



high



340



510



680



850



1020



1360



1700



2040



2380



Medium



280



390



520



640



790



1030



1290



1500



1800



low



180



260



350



430



520



690



860



1030



1200



Rated cooling capacity


W



high



1980



 



3680



4980



5580



7200



9900



10800



12600



Medium



1631



2279



2814



3750



4322



5534



7512



8088



9681



low



1048



1519



1894



2519



2854



5534



5008



5554



6454



Rated heat


W



high



2980



4800



5480



7200



8180



10800



14500



16200



18900



Medium



2454



3671



4191



5421



6335



8179



11005



12353



14521



low



1578



2447



2821



3600



4481



5479



7335



8482



9681



The input power



W



34



50



58



72



92



126



128



152



198



The amount of water


m3/h



0.42



0.52



0.62



0.86



0.98



1.08



1.58



1.78



1.92



Water press loss


Kpa



14



14



16



18



22



25



39



44



46



Motor number



1



2



3



4



 



power



220V~240/50HZ


 

 


1. The rated air volume refers to the outlet static pressure of 0Pa.
2. Cooling operation parameters: inlet air dry bulb temperature is 27℃, humidity temperature is      19.5℃, outlet water temperature is 7℃, return water temperature is 12℃.
3. Heating condition parameters: inlet air dry bulb temperature is 20℃, inlet water temperature      is 60℃, outlet water temperature is 50℃.


 fan-coil unit10.jpgfan coil unit.jpgfan coil unit 13.jpgfan coil unit 134.jpg


 



Our Services


 Pre-Sales Service
*Tell customers how to use our products and matters needing attention.
* Guide customers to choose the best and economic product, recover the                               investment within short time. .
* Site inspection if you need.


 


After-Sales Service
* If the project needs our installation guidance, we can send our engineer


and translator. We can also send customers installation video to teach them


how to fix and operate with our product.
*Usually, our product warranty is 36months after leaving factory . within


this months, all parts broken will be responsible for our factory.




 